    Product Details:

    Place of Origin: WenZhou, China
    Brand Name: SEFIE
    Certification: CB,CCC,ROHS
    Model Number: SF30LE-32

    Payment & Shipping Terms:

    Minimum Order Quantity: 2000-3000
    Price: Negotiable
    Packaging Details: 240 pcs per carton, 12pcs per box
    Delivery Time: 14 days after receipt of deposit
    Supply Ability: 200000 pcs per month
    Contact Now
    Detailed Product Description
    Material: Plastic Pole: 1P+N
    Tripping Curve: B,C,D Rated Voltage: 240
    Rated Current: 6,10,16,20,25,32 Color: White
    High Light:

    residual current circuit breaker with overcurrent protection

    ,

    earth leakage circuit breaker

     

    6-32amp 230V 3KA SF30LE-32 RCBO Earth Leakage Circuit Breaker

     

     

    1.  Provides comprehensive protection to household and commercail distribution systems

    2.  Provides protection against over-voltage

    3.  Equipped with switched neutral and phase pole

    4.  Effetively protects electric equipment against insulating failure

    5.  Provides complementary protection against direct contact by human body.

     

     

     

    Test procedure Type Test current Inital State Tripping or Non-tripping Time Limit Expected Result Remark
    a B,C,D 1.13In cold t≤1h no tripping  
    b B,C,D 1.45In after test a t<1h tripping current in the 5s in the increase of stability
    c B,C,D 2.55In cold 1s<t<60(In≤32A) tripping  
    d B 3In cold t≤0.1s no tripping turn on the auxiliary switch to close the current
    C 5In
    D 10In
    e B 5In cold t<0.1s   ture on the auxiliary switch to close the current
    C 10In
    D 50In
    The terminology "cold state"refes to that no load is carried brfore testing at the reference setting temperature

     